Evidence for Dutyholders

A useful EICR is more than a pass-or-fail document

The inspection should establish the condition of the installation within an agreed scope, identify safety concerns and leave records that support proportionate maintenance. We agree access, limitations and operational constraints before testing begins — and write reports that facilities teams, not just electricians, can act on.

Scoped
Extent and limitations agreed
Recorded
Circuit results and observations
Planned
Findings prioritised for action
What’s Included

Commercial Testing With Clear Records

Inspection and testing is carried out to BS 7671 and recognised industry guidance. We plan the work around the building, distribution system and operational needs. The report records what was inspected and tested, any limitations, the observations raised and the recommended interval to the next inspection.

Incoming supply and main switchgear
Distribution boards and protective devices
Earthing and protective bonding
Fixed wiring, containment and accessories
Lighting and power circuits
Isolation and switching arrangements
Recorded test results for every circuit tested
C1, C2, C3 and FI observations
Clear limitations and inaccessible areas
Separate remedial quotation where requested

Typically carried out for facilities managers, schools and academies, commercial landlords and managing agents, and office, retail and hospitality operators.

How It’s Delivered

From First Call to Final Report

1

Discussion and site review

We talk through how the building is used, occupancy, working hours, the number and location of distribution boards and any operational or safety constraints. Where possible we visit before quoting so testing can be planned in sensible phases.

2

Pre-inspection information pack

You receive a written scope, our proposed working approach, access requirements and site-specific considerations. We’ll usually ask for:

  • access to electrical rooms, risers and plant areas
  • your asbestos register
  • previous EICRs, drawings or circuit charts, if available
  • site rules, permits and any keyholder or escort arrangements
3

Inspection and testing

Visual inspection of the installation, dead testing with circuits safely isolated in an agreed sequence, and live testing to confirm protective measures. We keep your site contact informed throughout, so staff know what is happening and when.

4

Digital report and certification

The report is issued through NICEIC’s cloud-based certification platform, giving you secure digital records, a clear audit trail and a certificate that can’t be altered once issued. It’s written so both technical and non-technical stakeholders can see the priorities.

5

Prioritised findings and next steps

We explain the findings, which items need action now, which can be planned and which simply need monitoring. Where you want it, we provide an itemised remedial quotation per observation.

Understanding the Report

Observation Codes Explained

C1

Danger present. Risk of injury. Immediate action required — we will make safe or tell the dutyholder straight away.

C2

Potentially dangerous. Urgent remedial action required.

C3

Improvement recommended. Does not by itself make the report unsatisfactory.

FI

Further investigation required without delay, where an apparent deficiency could not be fully assessed. Under Amendment 4 it no longer automatically makes the report unsatisfactory.

Any C1 or C2 observation makes the overall report unsatisfactory, and a report with only C3 observations can still be satisfactory. Under BS 7671 Amendment 4, an FI no longer automatically makes a report unsatisfactory: the inspector decides, based on what the FI could conceal, and records the reasoning in the report.

What We Commonly Find

Typical Findings in Commercial Installations

Missing or inadequate protective bondingAgeing or incorrectly rated protective devicesMissing RCD protection where now requiredPoor or outdated circuit identificationBoards overloaded after alterationsDamaged accessories or containmentMixed standards from historic modifications
Maintenance and Compliance Records

Support for Planned Electrical Maintenance

The Electricity at Work Regulations require electrical systems to be maintained so far as is reasonably practicable to prevent danger. HSE guidance identifies inspection and, where necessary, testing as an essential part of preventive maintenance. An EICR can support that process, but it does not by itself discharge every duty or replace ongoing maintenance.

Commercial inspection intervals are not set by one universal rule. IET guidance suggests typical maximum intervals — for example five years for offices, shops and educational buildings and three years for industrial premises — but the right interval depends on the installation, its use, environment, condition, previous findings and any dutyholder, insurer or sector requirements. The inspector records the recommended date in the report.

Where records are incomplete, we can combine testing with electrical asset mapping and consistent board identification so future maintenance teams can understand the distribution system more quickly.

For Facilities Managers

What good electrical support should look like

Planning agreed before anyone arrives
Minimal disruption to building users
Honest reporting that explains risk properly
Accurate labelling and board identification
Records the next contractor can use
Practical advice, not unnecessary alarm
Common Questions

FAQs — Commercial EICR

How often does a commercial property need an EICR?
There is no single interval that suits every commercial installation. IET guidance suggests typical maximum intervals, such as five years for offices, shops and schools and three years for industrial premises, but the inspector should set the next date based on the building’s use, environment, condition and previous findings.
Will testing disrupt the building?
Some tests require circuits to be isolated. We agree access, critical loads and a practical sequence in advance so disruption can be managed and limitations recorded.
Can you test outside normal hours?
Where required, scheduling can be discussed during scoping. Availability and any additional arrangements are confirmed in the written quotation.
How long does a commercial EICR take?
It depends on the size of the installation, the number of boards and circuits, and access. Larger premises are often inspected in planned phases. The expected time on site is set out in the quotation.
What happens if defects are found?
The report records and classifies observations. We explain the findings and can provide a separate remedial quotation; urgent danger is brought to the dutyholder’s attention promptly.
Does a C3 observation mean the installation is unsafe?
No. C3 means improvement is recommended, and a report with only C3 observations can still be satisfactory. Any C1 or C2 observation makes a report unsatisfactory. Under BS 7671 Amendment 4, an FI no longer automatically does; the inspector decides and explains why.
Can you identify poorly labelled boards and circuits?
Yes. Circuit and asset identification can be included in the agreed scope. For larger or poorly documented sites, our Electrical Asset Mapping service may be appropriate.
Does an EICR guarantee legal compliance?
No single report guarantees compliance with every legal or operational duty. It provides evidence about the condition of the fixed electrical installation within its stated scope and limitations.
What premises do you cover?
We undertake agreed commercial inspection work for offices, schools, managed properties and other suitable premises across London and the South East.
Request a Site Assessment
Alan Woodhams
NICEIC Approved · Chislehurst
Clear scope · Written quote · Appropriate certification where required
★★★★★

“My family and I have used Alan many times over the years. He always does a brilliant job every time and is very knowledgeable. I couldn’t recommend Inspect Electrical enough!”

Katie
Google Review
Plan Your Fixed-Wire Testing

Commercial EICR — London & the South East

NICEIC Approved Contractor · Defined testing scope · Clear digital reporting and maintenance records

Call Alan
Based in
Chislehurst, SE London
Response
We aim to reply within 1 business day
Scroll to Top