BS 7671 Amendment 4:2026 — The Complete Technical Guide

📅 Published: 15 April 2026 ✍️ By Alan Woodhams, NICEIC Registered Electrician 🕐 12 min read
BS 7671 Amendment 4 was officially published today — 15 April 2026. This is the most significant update to the IET Wiring Regulations since Amendment 2 overhauled consumer unit and RCD requirements in 2022. Here is a complete technical breakdown of every major change, what it means in practice, and what you need to do before the October deadline.

1. What is Amendment 4 and why does it matter?

BS 7671 — the Requirements for Electrical Installations — is the UK national standard jointly maintained by the IET and BSI. It is the primary way the industry demonstrates compliance with the Electricity at Work Regulations 1989. Amendment 4 is the fourth update to the 18th Edition since its original publication in 2018, and it is issued as a second full consolidated edition — known in the industry as the Orange Book — absorbing all previous amendments (A1, A2, A3) into a single document.

This is not a minor correction. Amendment 4 introduces completely new chapters and sections that did not exist before, reflecting just how rapidly the electrical landscape has changed since 2022. Battery energy storage, Power over Ethernet, and smart ICT infrastructure have all moved from niche applications to everyday installations — and the regulations are now catching up.

Chapter 57

Stationary secondary battery installations — first dedicated battery chapter in BS 7671 history

Section 716

Power over Ethernet and ELV DC distribution via structured cabling

Section 545

Functional earthing for ICT systems — formalises FE vs PE distinction

Chapter 81

Energy efficiency framework — introductory but signals direction of travel

Section 710

Medical locations — completely overhauled and aligned with IEC 60364-7-710:2021

Chapter 65 / EICR

Updated documentation requirements, FI code clarification, photographic evidence

2. Chapter 57 — Stationary Secondary Battery Installations

This is the headline change. Chapter 57 is the first dedicated chapter for battery energy storage systems (BESS) in BS 7671. Until now, there was no specific regulatory framework — designers and installers had to rely on PAS 63100, manufacturer instructions, and best practice guidance. That gap is now formally closed.

What does Chapter 57 cover?

The chapter applies to permanently installed secondary battery systems where the primary purpose is electrical energy storage and supply. This covers domestic battery storage (typically paired with solar PV), commercial BESS, and grid-connected battery arrays, including vehicle-to-home (V2H) and vehicle-to-grid (V2G) configurations.

It does not apply to batteries within pluggable UPS units, fire safety systems (BS 5839), emergency lighting systems (BS 5266), or central safety power supply systems.

⚠️ Key regulatory change — Regulation 570.6.7.203 Battery installations in dwellings must comply with PAS 63100 (Protection Against Fire of Battery Energy Storage Systems). In non-domestic buildings, location and fire protection must be determined by a fire risk assessment.

Protective devices for bidirectional energy flow

One of the most practically important requirements is that all protective devices must be suitable for two-way energy flow. This rules out many conventional unidirectional overcurrent devices that have been routinely applied to battery-backed circuits. Regulation 551.7.1 has been redrafted to require a suitable protective device wherever bidirectional flow is possible, and there is a new prohibition on connecting a source to the load side of an RCD under certain conditions.

Stationary batteries are now formally classified as generating sets under Regulation 551.7.2.1, not loads. The previous Regulation Group 551.8 has been deleted and its content migrated into Chapter 57.

Location, ventilation, and fire risk

The chapter is detailed on where battery systems can and cannot be sited:

  • Thermal runaway — fire risk mitigation measures must be appropriate to the battery chemistry. Lithium-ion and lead-acid present very different profiles.
  • Ventilation — adequate ventilation must be demonstrated, particularly for lead-acid systems which can produce hydrogen.
  • Escape routes — batteries must not be located where a fire would compromise means of escape. Loft installations common in legacy retrofits may now need revisiting.
  • Isolation — dedicated isolation procedures during maintenance and testing are required. Unlike a conventional supply, a BESS is a continuous energy source that cannot simply be switched off at the meter.
💡 Practical note for NICEIC-registered businesses Chapter 57 formalises much of what the industry has been doing under PAS 63100 and MCS requirements. The key shift is that these requirements are now in BS 7671 itself — making them inspectable items on any EICR and a direct compliance requirement for new installations from October 2026.

3. Section 716 — Power over Ethernet (PoE)

Power over Ethernet has become a mainstream delivery mechanism for LED lighting drivers, IP cameras, access control, BMS sensors, and small appliances in commercial buildings. Despite widespread deployment, BS 7671 had no specific framework for PoE installations. Section 716 addresses this directly.

The voltage limits — read carefully

Standard BS 7671 SELV and PELV limits are 50 V AC and 120 V DC. Part 7 special location sections can modify these, and Section 716 does so significantly:

Location Section 716 Limit Standard PELV Limit
Dry locations 60 V ripple-free DC 120 V DC
All other locations (damp, outdoor, etc.) 15 V ripple-free DC 120 V DC

The 60 V limit in dry locations accommodates PoE++ (IEEE 802.3bt Type 4) which can deliver up to 90 W per port. The 15 V limit elsewhere reflects the increased hazard from DC in damp environments.

Cable and connector requirements

All PoE electrical connections must comply with BS ISO/IEC 11801-1 and must be capable of supporting a continuous operating current of 750 mA per contact. This is a specific and testable requirement. Key practical implications:

  • Where existing telecoms cabling is repurposed for PoE, it must be assessed for suitability — conductor CSA, connector ratings, and patch panel terminal ratings all need checking
  • Power sourcing equipment (PoE switches and injectors) must comply with BS EN 62368-3
  • PoE systems must be tested for both data performance and electrical safety compliance
⚠️ Commercial electricians — action required Any PoE infrastructure installed in commercial premises is now a regulatable item. If you carry out EICRs on smart buildings, offices, or schools, PoE systems must be assessed for cable suitability and voltage compliance from October 2026.

4. Section 545 — Functional Earthing for ICT Systems

Modern ICT infrastructure requires both protective earthing (for shock protection) and functional earthing (for signal integrity and EMC compliance). Until Amendment 4, there was no dedicated BS 7671 provision for functional earthing, creating uncertainty particularly around separate earth electrodes for IT equipment and the interaction between FE and PE conductors.

The core principle

⚠️ Critical requirement Interruption of the functional earthing must not in any way compromise or affect the protective earthing. Both systems must maintain independent integrity at all times.

What Section 545 introduces

  • Minimum conductor CSA for functional bonding conductors
  • Identification requirements — FE conductors must be clearly distinguishable from PE conductors
  • Main functional earthing terminal (MFET) — the ICT equivalent of the main earthing terminal
  • Equipotential bonding ring conductors — for data centres and broadcast environments requiring a consistent reference potential
  • Combined PE/FE conductors — permitted, but with specific requirements on CSA and identification

This section is directly relevant to school, hospital, commercial, and industrial installations where structured cabling and server infrastructure co-exist with conventional electrical systems.

5. Section 710 — Medical Locations

Section 710 has been completely overhauled to align with IEC 60364-7-710:2021 and its CENELEC adoption. This is the most substantive revision of any existing section in Amendment 4.

Revised group classification

Group Definition Examples
Group 0 No medical electrical equipment used on patients Waiting rooms, offices, car parks, reception
Group 1 Medical equipment used on intact skin or in procedures not involving cardiac connection Examination rooms, physiotherapy, minor treatment
Group 2 Procedures where interruption of supply could be immediately life-threatening Operating theatres, ICUs, cardiac catheterisation, angiography

Group 2 requirements

Group 2 locations attract the most demanding requirements under the revised section:

  • Medical IT systems — a transformer and insulation monitoring device (IMD) must be installed to maintain supply during a first fault. The IMD alerts staff before disconnection on a second fault, maintaining the principle that a Group 2 supply must never fail silently.
  • Two independent supplies — mandatory for Group 2 to eliminate single-point failure
  • UPS — must be provided and positioned as close as possible to the equipment it supports, minimising the length of potentially vulnerable cabling
  • Supplementary bonding test schedule — a new requirement to record resistance measurements of supplementary protective equipotential bonding conductors; this must be included in all commissioning and periodic inspection documentation

6. Other Notable Changes

Chapter 81 — Energy Efficiency (new, introductory)

Chapter 81 introduces a framework for energy efficiency in LV installations, aligned with the UK’s net-zero trajectory. At this stage it is advisory — following Appendix 17 guidance on power factor correction and circuit layout is not mandatory. However, this signals clear direction of travel, and the expectation is that future editions will strengthen these provisions as the regulatory landscape around building energy performance evolves.

Regulation 521.5.1 — Ferromagnetic enclosures

A clarifying note has been added: for switchgear and controlgear assemblies complying with BS EN IEC 61439, conductors carrying up to 200 A may pass through separate apertures in ferromagnetic enclosures. Above 200 A through separate holes, a temperature-rise test must confirm safe operation.

Regulation 521.10.202 — Cable support in fire conditions

A new note clarifies that the intent of this regulation is to prevent hanging or collapsed cables from blocking escape routes or impeding firefighting — it is not a requirement for circuit integrity of general wiring. Fire survival requirements remain in Chapter 56, BS 5839, BS 5266, and BS 8519.

Section 537 — Firefighter’s switches

Regulation 537.4.2 now requires firefighter’s switches to be located in positions identified by the fire engineer as part of the building’s fire strategy. This formalises the requirement for collaboration between electrical designers and fire engineers. Regulation 537.4.2.1 has been deleted.

Section 551 — Low-voltage generating sets

Significant revisions reflect the reality of bidirectional energy systems. Regulation 551.7.1 has been redrafted with a new requirement for suitable protective devices in bidirectional flow scenarios, and a prohibition on connecting a source to the load side of an RCD under certain conditions. Regulation 551.7.2 has been split into two separate regulations.

Chapter 65 — EICR documentation

  • EICRs must now include recipient guidance based on the Appendix 6 model
  • Photographic and thermographic images may be appended as supporting evidence — now formally acknowledged in the regulations
  • Signatures must be from those conducting the inspection and authorising the report
  • Important: issuing a Further Investigation (FI) code does not automatically result in an Unsatisfactory outcome — overall condition must be assessed on its merits

Appendix updates — cable rating data

New current-carrying capacity data has been added for buried cables installed in ducts, enabling more accurate volt drop and cable sizing calculations rather than relying on conservative assumptions.

7. Qualifications and Competency

City & Guilds

Current: 2382-22 (18th Ed. + A3)

Amendment 4: 2382-26

Transition: Both exams available April–October 2026. Only 2382-26 from 16 October 2026.

EAL

Current: Level 3 Award (A3-aligned)

Amendment 4: New Level 3 Award launched April 2026

Transition: Current qual closes for registration 31 July 2026; closes for certifications 31 December 2026.

NICEIC / Scheme Membership

Access to BS 7671:2018+A4:2026 (the Orange Book) must be demonstrable to maintain NICEIC certification from 15 October 2026.

Scheme rules require registered businesses to work to the current edition. During the transition period, the previous edition remains acceptable.

If you already hold the 18th Edition qualification, a focused one-day Amendment 4 update course is the accepted route — no need to resit the full exam. Training providers will be under pressure from late summer as the October deadline approaches. Book early.

8. Key Dates at a Glance

Date What happens
15 April 2026 Orange Book published — can be implemented immediately
15 Apr – 15 Oct 2026 Transition period — both A3 and A4 accepted; both C&G exams available
31 July 2026 EAL current qualification closes for new registrations
15 October 2026 Brown Book officially withdrawn. A4 is the sole recognised standard. NICEIC requires access to the Orange Book.
31 December 2026 EAL current qualification closes for certifications

Working on BESS, commercial, or healthcare installations?

Amendment 4 introduces new inspectable requirements across battery storage, PoE systems, ICT earthing, and medical locations. If you need fixed wire testing, EICRs, or electrical compliance work carried out to the latest standard — get in touch.

Frequently Asked Questions

When does BS 7671 Amendment 4 become mandatory?

Amendment 4 can be used immediately from 15 April 2026. The previous edition (BS 7671:2018+A2:2022+A3:2024) is withdrawn on 15 October 2026. After that date, all new installations must comply with Amendment 4.

Do I need to buy the Orange Book?

Yes. Unlike Amendment 3 which was a free PDF bolt-on, Amendment 4 is a full paid publication. It replaces the Brown Book and the Amendment 3 PDF. NICEIC will require you to demonstrate access to the Orange Book from October 2026 to maintain your registration.

Will my existing 18th Edition qualification still be valid?

Your qualification remains valid, but you will need to complete an Amendment 4 update course (typically one day) before October 2026 to ensure your knowledge reflects the current standard. City & Guilds and EAL are both launching updated qualifications.

Does my existing battery storage installation need to be changed?

Existing installations are not automatically non-compliant. However, if they are inspected under an EICR after October 2026, they will be assessed against Chapter 57 requirements — particularly around isolation, ventilation, fire risk, and documentation. It is worth reviewing any domestic BESS installations now.

Does Amendment 4 affect domestic solar PV installations?

Yes, where battery storage is involved. The new Chapter 57 requirements apply to battery systems paired with solar PV. PV-only systems without storage are largely unaffected by the Amendment 4 changes, though the broader Sections 551 and 712 updates are worth reviewing.

What does the FI code change mean for EICRs?

Amendment 4 clarifies that issuing a Further Investigation (FI) code does not automatically make the overall EICR result Unsatisfactory. The condition of the installation must be assessed holistically. This is a clarification of what should already have been good practice, but it now has explicit regulatory backing.

Is Chapter 81 energy efficiency mandatory?

Not yet. Chapter 81 is an introductory framework. The supporting Appendix 17 guidance is advisory rather than mandatory at this stage. However, given the trajectory of the Future Homes Standard and building energy performance regulation, it is worth integrating these principles into your design practice now.

Scroll to Top